Fault phenomenon | Possible causes | Exclusion method |
5The water pump doesn't come out |
1. The inlet and outlet valves are not opened, the inlet and outlet pipelines are blocked, and the runner impeller is blocked 2.The running direction of the motor is wrong, and the motor speed is very slow due to lack of phase 3. Air leakage of suction pipe 4. The pump is not filled with liquid and there is air in the pump chamber 4. The inlet water supply is insufficient, the suction head is too high, and the bottom valve leaks 5. The pipeline resistance is too large and the pump selection is improper 6. The pipeline resistance is too large and the pump selection is improper |
1. Check and remove the blockage 2. Adjust the motor direction and tighten the motor wire 3. Tighten all sealing surfaces to remove air 4. Open the upper cover of the pump or open the exhaust valve to exhaust the air 5. Shutdown inspection and adjustment (this phenomenon is easy to occur in grid connected water pipe and use with suction head) 6. Reduce pipeline bends |
Insufficient pump flow |
1. Check by reason 1 2. The pipeline and impeller of pump passage are blocked, and the valve opening is not enough 3. The voltage is low 4. Impeller wear |
1. Press 1 to exclude 2. Remove the blockage and readjust the valve opening 3. Voltage stabilization 4. Replace impeller |
Too much power, |
1. Use in excess of rated flow 2. The suction head is too high 3. The pump bearing is worn |
1. Adjust the flow and turn down the outlet valve 2. Decrease 3. Replace the bearing |
Noise and vibration |
1. Stabilize the pipeline 2. Increase suction pressure and exhaust 3. Reduce the vacuum 4. Replace the bearing 5. Adjust according to 51. The pipeline support is not stable 2. Liquid mixed with gas 3. Cavitation 4. Bearing wear 5. Overload operation of motor |
1. Stabilize the pipeline 2. Increase suction pressure and exhaust 3. Reduce the vacuum 4. Replace the bearing 5. Adjust according to 5 |
Motor heating |
1. Excessive flow and overload operation 2. Local friction 3. The motor bearing is damaged 4. Insufficient voltage |
1. Turn down the outlet valve 2. Check and eliminate 3. Replace the bearing 4. Voltage stabilization |
Water pump leaking |
1. Mechanical seal wear 2. There are sand holes or cracks in the pump body 3. The sealing surface is not smooth 4. The mounting bolt is loose |